Capacity of destruction in weight: 60 Kg/h.

It should be able to operate not less than 10 hours/day

This incinerator must be able to destruct all combustible wastes produced by hospitals, private clinics, laboratories, institutes, etc…

Design Specification : Types A, B, C, D, and E of medical waste 

“PYROLYTIC” combustion, by controlling the gasification of waste.

The incinerator must avoid the release of black smoke and fine dust, (Smokeless) during the loadings.

It should be able to reduce the volume of wastes by 98%.

It should be able to hold emission in the second burn with gas residence of not less than 2 seconds.

The incineration should be completely free from visible smoke as well as offensive odours.

The lower calorific power (L.C.P) of this waste will be 3,500 kcal/kg

The Temperatures of combustion: Minimum will be 850oC and max 1400oC

Post combustion: >1100oC.

The Internal diameter of the Chimney: Ø 400 and its height: 8 m

The Volume of the combustion chamber: 1.200 L

The Dimension of the door for loading in cm: 70×70.

Burner operation should be Automatic On/Off

Fuel : diesel

The supplier must provide  necessary information for the best of  the installation

This incinerator with “PYROLYTIC” combustion must have:

A combustion chamber of waste:

* Perfectly tight door for the manual loading of waste. The loading should be Manual, Batch Load 

* A burner of lighting which the use is limited to the ignition of waste.

* Frontage of loading with door seals gone up on hinges, wheel of screw plug, flexible joint, and stuffing insulating out of refractory.

* The insulation of the combustion chamber should be composed of refractory bricks, having a high content of aluminium and insulates bricks in order to assure a minimum temperature on   the outside sheet metal.

* Composition of the refractory;

Refractory concrete :

. Thickness : ≥100 mm

. Nature: 42% of Al203

Insulate in fibrous panels :

. Thickness: ≥75 mm

Nature: Calcium silicate.

* Burner of lighting of waste, with fuel, standard mono-bloc casting guiding  plunging flame, lighting and safety of electronic ignition, permanent ventilation, electromagnetic sluice gate of regulation and isolating valve.

* Plate of combustion in Carborundum, avoiding the fixing of glass and slags. 

[ecwid widgets="productbrowser search categories" default_category_id="CATEGORY_ID" default_product_id="PRODUCT_ID" lang="EN"]

Explore More

Another challenge: disposing of waste

A single Ebola patient treated in a U.S. hospital will generate eight 55-gallon barrels of medical waste each day. Protective gloves, gowns, masks and booties are donned and doffed by

Norfolk incinerator bill wrangle could continue until after Christmas

Norfolk County Council voted by 48 votes to 30 to terminate the contract for the proposed incinerator at Saddlebow at an extraordinary meeting in April. Council officers had said that,

Hazardous situation: Incinerators at K-P’s major hospitals out of order

PESHAWAR: Even with clear rules which state hospital waste must be incinerated within 24 hours of its collection, incinerators at two major hospitals in Khyber-Pakhtunkhwa (K-P) are out of order